FULLTEST 3
EN - 82
RCD test (RCD)
RCD types / characteristics: AC, A or B / General, Selective or Delayed
Measurement modes: x1/2IN, x1IN, x2IN, xKIN (K = 4 B type, K=5 AC, A type),
I (RAMP), AUTO (sequence: x1/2, x1, xK)
Nominal currents: 10, 30, 100, 300, 500, 650 or 1000 mA
Accuracy of test currents (10 mA): - 10% / + 0% (IN/2)
+ 10% / - 0% (IN, 2IN, KIN)
Accuracy of test currents (301000 mA): - 5% / + 0% (IN/2)
+ 5% / - 0% (IN, 2IN, KIN)
Input voltage range / frequency: 100 265 V / (50 / 60 Hz) ± 0.5 Hz
Contact voltage limits: 25 V or 50 V selectable
Test current polarity: POSITIVE or NEGATIVE selectable
Test duration (ms) – TT/TN system:
IN
(mA)
×1/2 ×1 ×2 ×K AUTO RAMP
G, S, D G, S, D G S D G S D G S D G S D
10
30
100
AC 1000 1000 200 250 50 150
320
A 1000 1000 200 250 50 150
320
B 1000 1000 200 250
320
300
AC 1000 1000 200 250 50 150
320
A 1000 1000 200 250 50 150
320
B 1000 1000 320
500
AC 1000 1000 200 250 50 150
320
A 1000 1000 200 250 320
B 1000 1000 320
650
AC 1000 1000 200 250 50 150
320
A 1000 1000 200 250 320
B
1000
AC 1000 1000 200 250 320
A 1000 1000
B
Resolution: 1ms, Accuracy: ± (3% rdg + 2 ms)
Mains voltage UL/N, UL/PE:
Display range
(V)
Resolution
(V)
Accuracy
100 265
1 ± (3% rdg.)
Input resistance (UL/N, UL/PE): 450 k
Ramp test: YES, current range 10 110% of IN in steps of 5% of IN
AUTO TEST: YES, test steps are as follows:
- t/IN/2 (pos. polarity)
- t/IN/2 (neg. polarity)
- t/IN (pos. polarity)
- t/I
N (neg. polarity)
- t/5I
N, (pos. polarity)
- t/5IN (neg. polarity)